Outdoor Emergency Application Guide

Power Sources

Traditional building-mounted fixtures on generators or AC power systems can be used for both normal and emergency egress lighting. An emergency generator provides continuous AC power to the fixtures on the emergency circuit(s) during loss of normal power. An AC power system utilizes batteries and converts DC to AC power for the fixtures on the emergency circuit(s) during loss of normal power.

When using incandescent or fluorescent lamps for emergency egress lighting, an emergency generator or interruptible AC power system can be used. If using HID lamps, a fast-transfer AC power system or uninteruptible power supply is required to switch the power quickly enough so that the HID lamp does not lose its arc and extinguish.

Power Source
System Type
Lamp Type Lamp Watt Start Temp (°F)* Lamp Life (in hours)* Lamp Lumens (initial)*
Generator/Interruptible AC
Power System
 
An emergency generator provides continuous AC power to the fixtures on the emergency circuit(s) during loss of normal power.

 
When using incandescent or fluorescent lamps for emergency egress lighting, an emergency
generator or interruptible AC power system can be used.
Incandescent
 

Compact Fluorescent

75A19 n/a 750 1,210
100A19 n/a 750 1,750
26DTT -5 12,000 1,800
26TRT -5 12,000 1,800
32TRT -5 16,000 2,400
42TRT -5 16,000 3,200
Fast Transfer
AC Power System
 
An AC power system
utilizes batteries and converts DC to AC power for the fixtures on the emergency circuit(s) during
loss of normal power.

 

If using HID lamps, a fast transfer AC power system or uninteruptible power supply is required to switch the power quick enough so that
the HID lamp does not lose its arc and extinguish.
HPS

 

 

 

 

 

Metal Halide

35S -40 24,000 2,250
50S -40 24,000 4,000
70S -40 24,000 6,300
100S -40 24,000 9,500
150S -40 24,000 16,000
200S -40 24,000 21,400
250S -40 24,000 27,000
50M -20 7,500 3,450
70M -20 11,250 5,000
100M -20 10,000 8,500
150M -20 10,000 12,500
175M (probe) -20 10,000 13,500
175M (pulse) -40 15,000 16,000
250M (probe) -20 12,000 20,500
250M (pulse) -40 15,000 23,150
  *Information taken from various lamp manufacturers' literature.